Encoder type, Table 23, Operating status – HEIDENHAIN PROFIBUS-DP (DPV0) User Manual
Page 47

Encoder and Gateway functionality, DPV0
47
5.6.3
Operating Status
Octet 9 in the diagnostic function provides information
about encoder-specific parameters. A class 2 encoder
sets the functionality bit for class 2 commands in order to
show the DP master that all class 2 commands are
supported. The DP master must activate the class 2
functionality bit in the parameter message (DDLM_Set_Prm)
to enable the use of class 2 functions. The status bit of
the scaling function is set when the scaling function is
activated and the resolution of the encoder is calculated
by means of the scaling parameters.
DDLM_Slave_Diag
Octet
9
Bits
7-0
Operating status
Bits
Definition
=0
=1
0
Code sequence
Increasing position
values for clockwise
revolutions (Seen from
flange side)
Increasing position
values for counter
clockwise revolutions
(Seen from flange side)
1
Class 2
functionality
No, not supported
Yes
2
Commissioning
diagnostics
No, not supported
Yes
3
Scaling function
status
Scaling disabled
Scaling enabled
4-7
Currently not assigned
Table 23
Operating status