beautypg.com

Class 2 functionality, Commissioning diagnostics, Scaling function control – HEIDENHAIN PROFIBUS-DP (DPV0) User Manual

Page 34

background image

Encoder and Gateway functionality, DPV0

34

5.4.1

Code sequence

The code sequence defines whether the absolute position value

should increase during clockwise or counter clockwise rotation of

the encoder shaft seen fromflange side. The code sequence is by

default set to increase the absolute position value when the shaft

is turned clockwise (0).

Note:

The position value will be affected when the code
sequence is changed during operation. It might be
necessary to perform a preset after the code
sequence has been changed.

5.4.2

Class 2 functionality

This bit enables or disables class 2 functionality. The Class 2

functionality bit for PROFIBUS-DP devices is by default disabled

(0). This means that this control bit must be activated during

parameterization in order to support the class 2 functions.

Note:

If a class 1 device uses some optional class 2
functions, the class 2 control bit must be set.

5.4.3

Commissioning diagnostics

The commissioning diagnostics function makes enable the device

to perform internal diagnostic test of the encoder components

responsible for position detection during a standstill of the

encoder (i.e. light unit, photovoltaic cells etc.). In conjunction

with the position alarms, it enables thorough checking of

whether the position values provided by the absolute encoder

are correct. The commissioning diagnostics function is started

by the commissioning bit in the operating parameters. If an

error is found within the absolute encoder, this is indicated in

the diagnostic function by the commissioning diagnostics

alarm bit (see chapter 5.6.2).

The commissioning diagnostics function is an option. To find out

whether the device supports commissioning diagnostics, the

“operating status” should be read by the diagnostic function

and the commissioning diagnostics bit should be checked.