Shielding philosophy, Gsd file, Table 4 – HEIDENHAIN PROFIBUS-DP (DPV0) User Manual

Page 16: Available gsd file for dpv0 gateway

background image

Encoder gateway installation

16

2.4

Shielding philosophy

To achieve the highest possible noise immunity and resistance

against other EMI related disturbances the bus and power supply

cables shall always be shielded. The screen should be connected

to ground on both ends of the cable. In certain cases

compensation current might flow over the screen. Therefore a

potential compensation wire is recommended.

2.5

GSD file

PROFIBUS Gateways can be configured and parameterized

corresponding to the requirements of the user. When the system

is started, the PROFIBUS devices are set and configured in

DDLM_Set_Prm mode, i.e the application class set by means of

the GSD file in the configuration tool and the operating

parameters are transferred to the respective slave.

Available GSD files can be downloaded from

www.heidenhain.com

GSD file

Gateway functionality

GSD file

Gateway PROFIBUS DPV0

(For rotary encoders)

ENC_A400

Table 4

Available GSD file for DPV0 gateway

When configuring the gateways two device classes (Class 1
or Class 2) can be selected as described in chapter 4.

Selectable parameters and functionality of the device depend
on the selected encoder class. This data, saved in the

PROFIBUS master is transferred once to the gateway when
the system is powered on. If the gateway has been started

with one GSD file and a new GSD file with a different ID-
number shall be used, the gateway needs to be restarted
before it can use the new GSD file.


After the configuration and parameter data have been received,

the gateway enters normal operation with cyclic data transfer i.e.

“DDLM_Data_Exchange mode”.