Encoder and Gateway functionality, DPV0

37

5.4.6

Total measuring range (units)

The total measuring range is defined by the parameter “Total

measuring range in measuring units.” The device has two

different operating modes, depending on the specified measuring

range. When the device receives a parameter message, it checks

the scaling parameters if a binary scaling can be used. If binary

scaling can be used, the device selects operating mode A (see

following explanation). If not, operating mode B is selected.

A. Cyclic operation (Binary scaling)
Cyclic operation is used when operating with 2

x

number of turns

(2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048. 4096.. number of

turns). If the desired total measuring range is equal to the

specified single turn resolution * 2

x

(where x<= 12) the encoder

operates in endless cyclic operation (0 - max - 0 -max..). If the

position value increases above the maximum value by rotating the

encoder shaft, the encoder continues from 0.

Example of a cyclic scaling:
Total measuring range = Measuring units per revolution x number

of revolutions


Measuring units per revolution = 1000

Total measuring range = 32000 (2

5

= number of revolution 32)

Figure 14

Cyclic scaling