beautypg.com

Node address, Figure 2, Pcb-view of a cable gland profibus gateway – HEIDENHAIN PROFIBUS-DP (DPV0) User Manual

Page 10

background image

Encoder gateway installation

10

2.1.1

Node address

The node address of the encoder gateway can be set via three

decimal rotary switches located inside the back cover. The

weighting, x100, x10 and x1 are specified on the circuit board

besides the switches. Permissible address range is between 0

and 126 but the lower addresses 0 to 2 are usually used by the

master and not recommended to be used by the device. Each

address used in a PROFIBUS network must be unique and may

not be used by other devices.

The device address is only read and adopted when the gateway

power supply is switched on. A restart of the gateway is therefore

required in order to adopt changes done to the address settings.

Figure 2

PCB-view of a cable gland PROFIBUS gateway

Example

: To set the node address to 115, the switch to the left

(x100) shall be set to 1, the switch in the middle(x10)

should also be set to 1 and the switch to the right(x1)

shall be set to 5.

Screw terminals

Bus termination

switch (on/off)

Node address

switches ()