Rosemount 3300 Series

4-2

CONFIGURATION
PARAMETERS

The Rosemount 3301 transmitter can be configured for level and volume
measurements. The Rosemount 3302 is designed to measure interface level
and interface distance as well.

The 3300 transmitter can be pre-configured according to the ordering
specifications in the Configuration Data Sheet.

Basic Configuration

The basic transmitter configuration includes setting the tank geometry
parameters. For interface measurements the dielectric constant of the top
liquid must also be given. For some applications with heavy vapor, the vapor
dielectric must be given as well.

Figure 4-1. Tank Geometry

Figure 4-2. Upper Reference
Point

For the different tank connections the Upper Reference Point is located at the
underside of the threaded adapter or at the underside of the welded flange, as
illustrated in Figure 4-2:

4mA

20mA

Reference Gauge
Height

Upper Null Zone

Product Level

Upper Reference Point

Lower Reference Point

Interface
Level

Probe
Length

T

A

NK GEOMETRY

NPT

BSP (G)

FLANGE

Upper Reference Point

3300

_UPPE

RR

E

F

ERENCE_B

A.

EP

S

Adapter