beautypg.com

2 troubleshooting, 3 cleaning rules, 2 troubleshooting 16.3 cleaning rules – ARAG GCS 3200 User Manual

Page 41: Maintenance / diagnostics / repairs

background image

41

16.2

Troubleshooting

fault

cause

reMedy

Valve controls take no effect

Valves not connected

• Connect the IN-CAB cable

(Chapter 9).

One valve does not open

No power supply to valve

• Check valve electric connection and operation.

The display no longer shows the speed

Wrong setup

• Check the setup of the wheel constant

(Par. 13.1).

No signal coming from the speed sensor

• Check connections to speed sensor

(Par. 8.4).

The displayed speed is not precise

Wrong setup

• Check the setup of the wheel constant

(Par. 13.1).

Output volume readout inaccurate

Wrong setup

• Check boom width setting

(Par. 12.4).

• Check the setup of the flowmeter constant

(Par. 12.6).

• Check the setup of the wheel constant

(Par. 13.1).

• Check the setup of the section valve type

(Par. 12.5).

• Check connections to speed sensor

(Par. 8.4).

Sprayed surface displayed does not match
actual sprayed surface

Wrong setup

• Check boom width setting

(Par. 12.4).

• Check the setup of the wheel constant

(Par. 13.1).

• Check connections to speed sensor

(Par. 8.4).

Covered area count not reset

• Reset counter.

(Par. 14.2.1).

Distance traveled count displayed does not
match actual distance covered

Wrong setup

• Check the setup of the wheel constant

(Par. 13.1).

• Check connections to speed sensor

(Par. 8.4).

Distance travelled count not reset

• Reset counter

(Par. 14.2.1).

Sprayed fluid count displayed does not match
litres/gpm actually sprayed

Wrong setup

• Check the setup of the flowmeter constant

(Par. 12.6).

• Check the setup of the section valve type

(Par. 12.5).

Distance travelled count not reset

• Reset counter

(Par. 14.2.1).

Three-way section valves in use, but no backflow
calibration

• Perform calibration.

Time count displayed does not match actual
time worked

Work time count not reset

• Reset counter

(Par. 14.2.1).

Spray volume set for automatic operation
cannot be achieved

Wrong setup

• Check spray rate setup

(Par. 13.2).

• Check boom width setting

(Par. 12.4).

System not adequately sized to provide required
rate

• Check maximum pressure valve setting.
• Make sure control valve is adequate for specific system.

Control valve malfunction

• Check valve operation.

Instantaneous pressure readout inaccurate

Wrong setup

• Check pressure sensor full scale setting

(Par. 12.7).

Pressure sensor not calibrated

• Perform calibration

(Par. 14.3).

Pressure sensor improperly installed

• Check connections to pressure sensor

(Par. 8.4).

Instantaneous pressure not displayed

Wrong setup

• Check pressure sensor setting

(Par. 12.7).

Computer receives no signals from speed sensor

• Check connections to pressure sensor

(Par. 8.4).

Pressure sensor improperly installed

• Check connections to pressure sensor

(Par. 8.4).

RPM readout inaccurate

Wrong setup

• Check RPM sensor constant setting

(Par. 12.11).

RPM not displayed

Computer receives no signals from RPM sensor

• Check connections to RPM sensor

(Par. 8.4).

RPM sensor improperly installed

• Check connections to RPM sensor

(Par. 8.4).

Pump failure alarm permanently active

Computer receives no signals from Pump
Protector sensor

• Check connections to Pump Protector sensor

(Par. 8.4).

Tab. 11

16.3

Cleaning rules

- Clean only with a soft wet cloth.
- DO NOT use aggressive detergents or products.
- DO NOT use water jets to clean the monitor and the control unit.

Fig. 101

MAINTENANCE / DIAGNOSTICS / REPAIRS