Proportional Band

When

displays on the

PV

screen, you can then change the proportional band (P constant)

by pressing

and

. The new value displays on the

SV

screen. You can set it in a range

from 0.1

°

to 999.9

°

C/

°

F in units of 0.l

°

C/

°

F. The value is set at the factory to 40.0

°

C/

°

F, but this

changes as the controller auto-tunes itself.

Integral

Time

When

displays on the

PV

screen, you can change the integral time (I constant) by

pressing

and

. You can set it in a range from 0 to 3,999 seconds in units of 1 second.

The value is set at the factory to 233 seconds, but this changes as the controller auto-tunes itself.

Derivative Time

When

displays on the

PV

screen, you can change the derivative time (D constant) by

pressing

and

. You can set it in a range from 0 to 3,999 seconds in units of 1 second.

The value is factory-set to 40 seconds, but this changes as the controller auto-tunes itself.

Manual Reset Value (%)

When using P or PD control (i. e. I = O), the process value may stabilize at a value above or
below the set point of the manual reset value, which has a factory default setting of 50%. You
can adjust it upward to eliminate droop or downward to eliminate overshoot.

Note: The

P

,

I

,

D

, and

OFR

parameters are not accessible when the control mode is set to PID

with fuzzy self-tuning; P, I, and D are set automatically to optimum values based on
current process conditions determined by the controller.

Page 66