5 Additional Level 2 Controller Features

5-1 Level 2 Control Panel

Optional

The optional Level 2 controller option operates identically to the standard Level 1 controller
covered in the previous chapter. However, this controller adds front-mounted

SYSTEM

START/STOP

and

TEMP. SET POINT NORMAL/SHIFT

switches and

Blower On

,

High Regen

Air Temp.

, and

Dirty Filter

indicators. The following page shows a typical Level 2 controller.


5-2 Level 2 Control Panel Indicator Lights

Process Heater On
The

Process Heater On

indicator lights when the process air heater is energized.


Hi-Process Air Temp
The

Hi-Process Air Temp

alarm indicator lights when the temperature at the process air

thermocouple is above the high alarm set value. This indicator lights when the alarm relay
energizes; all heaters turn off and the blower remains on.

The alarm mode and value are factory-set to track 25º above the process set point. The alarm
value is a deviation above the process set point. When the temperature at the process
thermocouple returns to within the acceptable range, the alarm output de-energizes and all
heaters turn on again automatically. You can adjust the alarm value; see Section 6-5 on Page 43
for more information.

WDMR and WDFR Series Dehumidifying Dryers

Page 33