Level 2 controllers, Press once to restore. 14. turn, Set the rotary-type alarm mode selector switch – AEC WD 350 through WD3000 Dehumidifying Dryers User Manual

Page 58: For upper limit alarm with standby, Set the rotary-type, Switch to position 0. this alarm is not used, Alarm value, Alm 1, Alm 2

background image

12. Press

and

to select a setting for Alarm 1, the high temperature alarm. The

factory setting is

25

.

13. Press

once to restore.

14. Turn

OFF

the power switch on the graphic display and remove all electrical power from

the dryer when you finish.


Figure 16

Level 1 Controller Factory Preset Parameters

Parameter

setting level

Parameter

description

LED

display

Process temperature display at power-up (°)

- Actual air temperature -

Process temperature set point (°)

0

Alarm value


Level 2 Controllers

If preset parameters on the controller have been tampered with and it no longer properly controls
temperature, you can restore it to the factory setup. Perform the following procedures to restore
factory setup:

1. Turn off the power switch on the graphic display and remove all electrical power to the

dryer.

2. Press up the latch at the bottom of the module front panel and slide out the control

chassis.

3. Locate the slide-type lockout switch marked Protect on the circuit board. It should be

OFF

.

4. Check to make sure that the control output relays are installed on the circuit board. Level

2 controllers use one E530S solid state relay (SSR) installed in the socket. This relay
switches the heaters on and off.

0

1

2

3

4

5

6

7

8

9

ALM-1

5. Set the rotary-type alarm mode selector switch

ALM 1

to position

2

for upper

limit alarm with standby.

0

1

2

3

4

5

6

7

8

9

ALM-2

6. Set the rotary-type

ALM 2

switch to position 0. This alarm is not used.

WDMR and WDFR Series Dehumidifying Dryers

Page 57