AEC WD 350 through WD3000 Dehumidifying Dryers User Manual
Page 59
7. Set the rotary-type
INPUT
selector switch to position
2
. WD Dryers are
factory-equipped with type K thermocouples; other temperature sensor types
can be used if the switch is properly set.
0
1
2
3
4
5
6
7
8
9
INPUT
Refer to the following table:
Switch Sensor
Temperature
range
setting type
°C
°F
0, 8
JPT100
-199.9 to 650.0
-199.9 to 999.9
1, 9
PT100
-199.9 to 650.0
-199.9 to 999.9
2 K
-200 to 1,300
-300 to 2,300
3 J
-100 to 850
-100 to 1,500
4 T
-199.9 to 400.0
-199.9 to 700.0
5 L
100 to 850
-100 to 1,500
6 U
-199.9 to 400.0
-199.9 to 700.0
7 N
-200 to 1,300
-300 to 2,300
Unit of measure is .1º (ºF or ºC). 100ºC/139.16
Ω
Unit of measure is .1º (ºF or ºC). 100ºC/138.50
Ω
Unit of measure is 1º (ºF or ºC)
8.
Function
selects between four (4) control modes. Put this switch
in the set-up configuration at right (all
OFF
) while entering
initial control parameters.
1
2
3
4
N
O
FUNCTION
Available functions are:
Function Switch number
Switch setting
Setting
ON Normal
(Cooling)
Control
Output
1
OFF Reverse
(Heating)
ON On/Off
Operation
2
OFF
Advanced PID Operation
ON
Manual PID Tuning
Control
Mode
3
OFF
Fuzzy Adaptive Tuning of PID
ON
Engineering Programming Menu
Menu 4
OFF
Standard Programming Menu
9. Slide the control chassis back into the control housing. Set remaining parameters with the
keypad.
10. Prepare your dryer for startup with a real or simulated load, then restore electrical power.
Page 58
WDMR and WDFR Series Dehumidifying Dryers