Channel Ouput Polarity

The next parameter on the front panel menu label is channel output polarity. To select this

parameter, release the push-button when the red LED comes on solid.

Note

This parameter can also be changed using the DIP switches or Click Supervisor.

This parameter lets you choose the polarity of the calls placed by the Click 111. A call can be

indicated by either high voltage or low voltage, depending on how you configure the device.

The Channel Output Polarity parameter affects both buses.

Level 1 LEDs

Channel Output Polarity

Level 2 LEDs

High asserted

Low asserted

LED off
LED on

Cancel and exit menu

Table 14 – Front Panel Menu Channel Output Polarity Settings

See the earlier Navigating through the Menu and the Menu Operation Example sections for

how to configure this parameter.

Because this parameter can also be set by the DIP switches, you may need to ensure that the

DIP switches are set to Software configuration mode; if they are set to Hardware, the front

panel menu will be able to display but not change these settings.

Fault Ouput Polarity

The next parameter on the front panel menu label is fault output polarity. To select this pa-

rameter, release the push-button when the yellow and red LEDs come on solid.

Note

This parameter can also be changed using the DIP switches or Click Supervisor.

This parameter is much like channel output polarity, except that it affects the polarity of

calls sent not based on detection but based on the Click 111 going into a fault state. When