beautypg.com

Visara Master Console Center Installation User Manual

Page 13

background image

Chapter 1 Introduction and Checklist

Installation Preparation Guide

13

10. Supply a printout of the addresses to Visara in input format (e.g.,

for each MVS LPAR, give the MVSCP entry, HCD NIPCON entry,

etc.).

11. Supply Visara with a copy of the “IPL and SHUTDOWN

PROCEDURES” for each LPAR the MCC will IPL. This is
typically a manual for operators, and/or a listing of the steps

necessary to perform some or all of these startup/shutdown

actions).

12. Supply Visara with a copy of the “SOFTWARE OPERATIONS

PROCEDURES” for each LPAR the MCC will monitor. This is

typically a manual for operators, and/or a listing of the steps that

current automation takes in performing some or all of these daily
operation actions).

13. Identify and supply a list of all software to be monitored for each

LPAR (e.g., for an MVS LPAR, use a “D A,ALL”, and check off

those address spaces that are to be active at all times (typically all
your started tasks, and potentially some batch jobs, especially if

you run CICS, etc.))

14. Identify the commands required to “start”, “stop normal ”, and

“stop abnormal” each task in question (e.g., “S IMSPROD”, “F
IMSPROD,SHUT IMMED”, “FORCE IMSPROD,ARM”). If

multiple commands are required (even if they must be issued on

multiple LPARS), be sure to supply ALL THE COMMANDS. For
example, it might be necessary to check that IMSPROD is down

on LPAR X prior to starting IMSPROD on LPAR Y - this takes

multiple commands).

15. Identify current “operational automation” to be replaced (e.g.,

supply Visara with your “AUTOMATE” listings) and any special

requirements you may have (e.g., “need to gather information

from multiple hosts in order to make an automation decision”,
etc.). Please supply the list in IEBCOPY format if feasible, rather

than on printed hardcopy.

16. If you want VTAM terminal emulation on the MCC server, please

indicate the number of terminals required.