beautypg.com

Refrigeration – Scotsman CME306 User Manual

Page 39

background image

Refrigeration

To use the access valves:
1. Be sure that the valve is closed. Remove the

stem cap and insert a 3/16" allen wrench. Check

that the valve is closed.
2. Remove the port cap and attach refrigerant

manifold hoses.
3. Open the valve and purge the hoses.
4. When service is complete, shut the discharge

access valve first. Then, with the machine running

and the middle hose outlet securely fastened to

the manifold or refrigerant tank (closed) open both

manifold valves. This allows any liquid refrigerant

in the discharge hose to flow thru the manifold and

into the suction side.
5. After the gages have equaled, shut the manifold

valves and the suction access valve.
6. Remove the gages and replace the stem and

port caps. Make certain that they are tightly closed.
Refrigeration System Components
Due to the expected level of training and

experience of a refrigeration mechanic, detailed

instructions regarding the replacement of

refrigeration components will not be presented.

However, critical items will be noted here.
Refrigerant:
1. This ice machine uses R-404A or HP62 as a

refrigerant. It has several unique characteristics.
A. It must use polyol ester refrigerant oil, and that

oil is very water absorbent. The system must not

be open for more than 15 minutes.
B. An electronic leak detector capable of locating

HFC-134a type refrigerant must be used to locate

refrigerant leaks.
C. An HFC type liquid line dryer must be used.
D. A nitrogen purge is required when brazing.
E. When evacuating, use of an electronic micron

gage is recommend. Evacuate to 300 microns.
F. It must be liquid charged:
1. Place a drum or cylinder of R-404A on the

scale, liquid out side up (check container).
2. Attach the charging hose to the cylinder of

R-404A. Open the cylinder’s valve and purge the

hose to the manifold.

3. Close the low side service access valve.
4. Open the discharge side manifold valve and

weigh in the name plate charge. After the charge is

weighed in, wait a moment & re-check the scale.
5. If all of the refrigerant charge has not been

weighed into the discharge side, it must be

carefully added thru the low side. Close the

discharge service access valve.
6. With a sight glass or charge faster in the hose to

the low side port, start the ice machine.
7. Open the low side service access valve.
8. Crack open the low side manifold valve and

watch the scale and sight glass. Open and close

the low side manifold valve to flow liquid into the

manifold but flash off to vapor before it enters the

refrigeration system.
9. After the scale = the correct charge, shut off the

valve on the refrigerant cylinder.
10. With the ice machine running and the

discharge access valve closed, open both manifold

valves to allow the refrigerant in the hoses to enter

the system.
11. Shut the suction service access valve.
12. Remove the refrigeration manifold gages.
13. Replace and tighten all caps.

CME306 & CME456

January 2000

Page 39

This manual is related to the following products: