Service Diagnosis: Components

CME306 & CME456

January 2000

Page 33

Problem or Symptom Possible Cause

Probable Correction

Fan motor does not

turn. Refrigeration light

may be on steadily or

blinks 3 times and

repeats.

Open motor windings, or

seized bearings

Replace fan motor

No power to fan motor

Fan motor unplugged, check for voltage from

controller. If none, replace controller.

Pump motor does not

turn

Open motor windings, or

seized bearings

Replace pump

No power to pump

Check electrical connections. If the unit is in

Freeze the pump should have power to it. If

not, replace the AutoIQ Controller.

Hot Gas Valve does

not open.

Open solenoid coil.

Replace hot gas valve

Stuck valve

Replace hot gas valve

No power to coil in Harvest Check wire connections, if ok, replace AutoIQ

Controller

Hot Gas Valve leaks

thru (warm tube

temperatures on both

sides of valve during

freeze)

Mechanical problem in

valve

Replace valve

Water Inlet Valve does

not open

Open solenoid coil

Replace valve

Stuck valve

Replace valve

No power to valve (early

part of harvest)

Check wire connections, if ok, replace AutoIQ

Controller

Water Inlet Valve does

not flow enough water

Restriction in water supply

Check water filters and/or inlet screen.

Water Inlet Valve

leaks thru

Mechanical problem in

valve

Replace valve

Compressor does not

work

Unit in Clean cycle

Push and release Freeze button.

Contactor coil open

Replace contactor

Open starting components

Check and replace

Open windings

Check and replace compressor

Internal valve failure

Replace compressor

Water level too low or not

sensed

Unit must be full of water before controller will

start compressor. Check water level and

sensor and harness.