Removal and Replacement: Water Level Sensor

1. Remove front panel.
2. Push and hold the OFF button. Release it when

the machine stops.
3. Unplug the wires from the sensor.
4. Remove one screw holding sump cover to

sump.
5. Unwind wires from sump cover.
6. Lift the cover enough to remove the float from

the stem.
7. Squeeze mounting tabs together to release

sensor from cover.
8. Reverse to reassemble.

Purge Valve Timer

The purge valve timer is sensitive to electrostatic

discharge. Be certain to touch a grounded surface

before touching this component. Do the same

when handling the replacement part.

1. Touch a grounded surface.
2. Remove front panel.
3. Disconnect electrical power.
4. Remove high voltage box cover.
5. Locate timer board at the bottom of the high

voltage box.
6. Unplug all the wires to the board.
7. Compress each of the four stand-off posts to

release the board from the stand-offs.
8. Remove the board from the unit.
Reverse to reassemble.

Water Temperature Sensor
Note: This sensor is replaced as a set with the

Discharge Temperature Sensor.
1. Remove front panel.
2. Push and release Off button.
3. Remove 1 plastic bolt and the reservoir cover.
4. Locate water temperature sensor (inserted into

pump discharge hose).
5. Pull out to remove.
6. Trace back to AutoIQ Controller, unplug from

#5.
7. Remove the Discharge Line temperature sensor

(see next).
8. Reverse to reassemble.

Discharge Line Temperature Sensor

1. Remove front panel, push and release the Off

button.
2. Locate discharge line sensor. It is attached to

the discharge line of the compressor, 6" from the

compressor discharge port.
3. Unwrap the insulation and un-snap the clip

holding the sensor to the discharge line.
4. Trace the sensor wires back to the controller,

they are plugged into #5 with the water

temperature sensor, and must be replaced with it.
5. Reverse to replace, be sure that the discharge

line sensor is 6" up from the compressor discharge

port. Be sure to re-wrap the insulation.
Note: Route wires so they do NOT contact the

discharge line.
The sensor for the Discharge line is marked

with a small piece of yellow tape. Do not

reverse the sensors.

CME306 & CME456

December 1999

Page 37