Removal and Replacement: Water Level Sensor
1. Remove front panel.
2. Push and hold the OFF button. Release it when
the machine stops.
3. Unplug the wires from the sensor.
4. Remove one screw holding sump cover to
sump.
5. Unwind wires from sump cover.
6. Lift the cover enough to remove the float from
the stem.
7. Squeeze mounting tabs together to release
sensor from cover.
8. Reverse to reassemble.
Purge Valve Timer
The purge valve timer is sensitive to electrostatic
discharge. Be certain to touch a grounded surface
before touching this component. Do the same
when handling the replacement part.
1. Touch a grounded surface.
2. Remove front panel.
3. Disconnect electrical power.
4. Remove high voltage box cover.
5. Locate timer board at the bottom of the high
voltage box.
6. Unplug all the wires to the board.
7. Compress each of the four stand-off posts to
release the board from the stand-offs.
8. Remove the board from the unit.
Reverse to reassemble.
Water Temperature Sensor
Note: This sensor is replaced as a set with the
Discharge Temperature Sensor.
1. Remove front panel.
2. Push and release Off button.
3. Remove 1 plastic bolt and the reservoir cover.
4. Locate water temperature sensor (inserted into
pump discharge hose).
5. Pull out to remove.
6. Trace back to AutoIQ Controller, unplug from
#5.
7. Remove the Discharge Line temperature sensor
(see next).
8. Reverse to reassemble.
Discharge Line Temperature Sensor
1. Remove front panel, push and release the Off
button.
2. Locate discharge line sensor. It is attached to
the discharge line of the compressor, 6" from the
compressor discharge port.
3. Unwrap the insulation and un-snap the clip
holding the sensor to the discharge line.
4. Trace the sensor wires back to the controller,
they are plugged into #5 with the water
temperature sensor, and must be replaced with it.
5. Reverse to replace, be sure that the discharge
line sensor is 6" up from the compressor discharge
port. Be sure to re-wrap the insulation.
Note: Route wires so they do NOT contact the
discharge line.
The sensor for the Discharge line is marked
with a small piece of yellow tape. Do not
reverse the sensors.