Technicians Only: Harvest Cycle Operational Sequence

Harvest

The (air cooled model) fan(s) is(are) off.
The purge valve opens, and will remain open for

40 seconds.
The water pump shuts off, it will restart in less than

40 seconds, depending upon the Purge Level set.
The water pump restarts and pumps out water thru

the open purge valve until the valve closes.
The inlet water valve then opens for about 22

seconds to add some water.
During the Harvest Cycle, ice will be falling from

the evaporators and between the ice sensor’s

electric eyes. The AutoIQ Controller monitors the

ice falling and stays in the Harvest Cycle until ice

quits going thru the electric eyes.
The maximum harvest time is 13 minutes. The first

Harvest after a restart will be a long one to

establish a base line, then the actual time it took to

release the ice is used to determine the length of

the next harvest cycle.
If no cubes fall (or are sensed) by the end of

Maximum Harvest Time, the machine senses a

refrigeration error. If the next cycle also produces a

refrigeration error, the machine Shuts Down.
Note: The last harvest cycle before shutting off on

bin full is 6 minutes long, unless the shut down

was initiated by a closed Bin Thermostat. In that

case the last harvest cycle will be normal.

The machine will not restart for 4 minutes after

switching off on Bin Full, unless the freeze button

is pressed.
Note: If during a Bin Full shut down, the machine

has not restarted for 12 hours, the compressor will

run for 30 seconds to clear its oil of refrigerant.

Continuous Run Time:
A unit that operates 24 hours a day 7 days a week

is too small for the user’s needs. To maintain

harvest integrity, the controller will extend the

harvest time up to 6 minutes every 15th

consecutive harvest cycle. Note: The length of this

harvest varies depending upon discharge temp.
Bin Thermostat (for those units so equipped):
In normal ambients the thermostat will react to ice

on the bulb in a few seconds. Reaction after

removal will take about a minute under normal

conditions, and longer in colder rooms.

Diagnostic Lights and Manual Resets

The controller will shut the machine off if a

malfunction is sensed. The Controller will restart

the machine 2 times, with a 50 minute interval

between restarts. If a malfunction is still present

after the second restart, the machine will then shut

off and must be manually reset. During the restart

interval, the machine will be off and a diagnostic

code indicated.
The exception to this is lack of water. The machine

will always try to re-fill the reservoir every 20

minutes.
Diagnostic Code Table

If a Diagnostic

Light

Water Light

Refrigeration

Light

Blinks once and

repeats

Water pump did

not start

Very long ice

harvest

Blinks twice and

repeats

Lack of water fill No harvest of

ice

Blinks three

times and

repeats

not used

High Discharge

Temperature

Is ON all the

time

Water valve

leaking thru

rapidly

Check for low

discharge

temperature or

long freeze

cycle

Both On all the

time

Check for thermistor set unplugged

or failed

Note: Diagnostic lights remain on until controller is

manually reset or until it successfully restarts the

machine.