XG00516-
150204
I-Series Indoor Gas Fireplace
Installation
Section 2: Installation
Figure 1 Sec.2
30DFID-S installation dimensions
8 12 "
216
16"
406
10"
254
Hearth Protection
Not Required
Side Wall
Mantel
Faceplate
Min
Figure 2 Sec.2 30FID-S Clearances
Install Dimensions:
The install size requirements of your fireplace insert are dependent
on several factors. Gas line location, electrical connection and
gas line type can play into what the minimum installation size
can be. The diagram below illustrates the smallest possible size
requirement of this model. Please take into consideration these
other factors when determining if this appliance will fit into your
masonry or manufactured fireplace.
A
A
20"
508mm
14"
356mm
30"
762mm
Gas and Electrical
supply on right side
B
B
20"
508mm
5"
127mm
The 30DFID-S Insert is designed and built to be installed into masonry or manufactured fireplaces. There is no requirement to
have a non-combustible hearth in front of the unit. Clearances to the underside of the mantel or sidewall are measured from the
edge of the door/screen front. The Mantel is shown as 10” maximum at a distance of 16” minimum from the door edge top. The
mantel can be extended further providing that you increase the height proportionately. For instance, if you want a mantel that is
2” beyond the 10” minimum, you have to install it 2” above the 16” minimum.
Clearances: