beautypg.com

Analog outputs, Digital i/o – Measurement Computing DaqBook 2000 Series User Manual

Page 83

background image

Specifications are subject to change without notice.

DaqBook/2000 and DaqOEM/2000 Series

898695

Specifications 11-5

5. Counter/Totalizer Triggering: Counter/totalizer inputs can trigger an acquisition. User can select to trigger

on a frequency or on total counts that are equal, above, below, or within/outside of a window.

Latency: One scan period maximum.

6. Software Triggering: Trigger can be initiated under program control.

Analog Outputs

Applies to DaqBook/2020, DaqBook/2001, and DaqOEM/2001
Does not apply to DaqBook/2005 or to DaqOEM/2005

Four analog output channels are updated synchronously relative to scanned inputs, and clocked from either an
internal onboard clock, or an external clock source. Analog outputs can also be updated asynchronously,
independent of any other scanning in the system.

Channels: 4 DAC channels (DAC0, DAC1, DAC2, and DAC3)

Resolution: 16 bits

Data Buffer: 256Ksample

Output voltage range:

±10 V

Output current:

±10 mA

Offset error:

±0.0045 V maximum

Digital Feedthru: 50 mV when updated

Gain error:

±0.01%

Update rate: 100 kHz maximum, 1.5 Hz minimum (no minimum with external clock)

Settling Time: 10

µs maximum to 1 LSB for full-scale step

Clock Sources: 4 programmable

1.

Onboard D/A clock, independent of scanning input clock

2.

Onboard scanning input clock

3.

External D/A input clock, independent of external scanning input clock

4.

External scanning input clock

Digital I/O

Channels:

DaqBook/2001, /2005: 40 built-in, expandable to 272 with external DBK options

DaqOEM/2001, /2005: 40 built-in, expandable to 272 with external DBK options

DaqBook/2020: 24 built-in, expandable to 256 with external DBK options

Input Scanning Modes: 2 programmable

1.

Asynchronous, under program control at any time relative to input scanning

2.

Synchronous with input scanning

Ports:

DaqBook/2001, /2005: 3 x 8-bit (82C55 emulation), and 1 x 16-bit, Programmable as input or output.

DaqOEM/2001, /2005: 3 x 8-bit (82C55 emulation), and 1 x 16-bit. Programmable as input or output.

DaqBook/2020: 3 x 8-bit (82C55 emulation). Each port is programmable as input or output.

Input Characteristics: 100

Ω series, 20 pF to common

Input protection:

±8 kV ESD clamp diodes parallel

I/O levels: TTL

Sampling Rate: 200 kHz max

Update Rate: Asynchronous under program control

Output Characteristics: Output 12 mA per pin, 200 mA total continuous (per bank of 24 outputs)