CB-7011/CB-7011D, CB-7018 User’s Manual

ignore the digital output command @AADO(Data).

3.6 High/Low Alarm

Some analog input modules, such as the CB-7011, are

equipped with a high/low alarm function. When the alarm function

is enabled, the digital output DO0 is the low alarm indicator, DO1

is the high alarm indicator, and the digital output command for chang-

ing digital outputs DO0, DO1 is ignored. The alarm function is to

compare the analog input value with given high alarm value and

low alarm value. And there are two alarm types as follows:

Momentary alarm: the alarm status is cleared when the analog

input is not over the alarm value.

If Analog Input Value > High Alarm, DO1 (High alarm) is on,

otherwise DO1 is off.

If Analog Input Value < Low Alarm, DO0 (Low alarm) is on,

otherwise DO0 is off.

Latch Alarm: the alarm is cleared only the user send com-

mand to clear.

If Analog Input Value > High Alarm, DO1(High alarm) is on,

else if Analog Input Value < Low Alarm, DO0(Low alarm) is

on.

3.7 Thermocouple Measurement

When two wires composed of dissimilar metal are joined

at one end and heated, the open circuit voltage is a function of the

junction temperature and the composition of the two metals. All

dissimilar metals exhibit this effect. The voltage is called Seebeck

voltage”. For small changes in temperature the Seebeck voltage is