37 ~aa4 – Measurement Computing CB-7011 User Manual
Page 59
59
CB-7011/CB-7011D, CB-7018 User’s Manual
2.37 ~AA4
Description: Read PowerOn Value and Safe Value
Note: The command is for CB-7011/11D/11P/11PD only
Syntax: ~AA4[CHK](cr)
~
delimiter character
AA
address of reading module (00 to FF)
4
command for reading PowerOn Value and Safe Value
Response: Valid Command:
!AAPPSS[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
PP
PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,
DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS
Safe Value, data format is same as PP
Example:
Command: ~014
Receive: !010000
Read address 01 Power-On/Safe Value, return Power-On Value
is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.
Related Command:
Sec. 2.38 ~AA5PPSS
Related Topic:
Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation