49

CB-7011/CB-7011D, CB-7018 User’s Manual

2.27 @AACA

Description: Clear Latch Alarm

Note: The command is for CB-7011/11D/11P/11PD only.

Syntax: @AACA[CHK](cr)

@

delimiter character

AA

address of setting module (00 to FF)

CA

command for clear latch alarm

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example:

Command: @01DI

Receive: !0120101

Read address 01 digital input, return latch alarm mode, low

alarm is set.

Command: @01CA

Receive: !01

Clear address 01 latch alarm, return success.

Command: @01DI

Receive: !0120001

Read address 01 digital input, return latch alarm mode, both

alarms are clear.

Related Command:

Sec. 2.21 @AADI, Sec. 2.23 @AAEAT, Sec. 2.26 @AADA

Related Topic:

Sec. 3.6 High/Low Alarm