beautypg.com

38 ~aa5ppss – Measurement Computing CB-7011 User Manual

Page 60

background image

60

CB-7011/CB-7011D, CD-7018 User’s Manual

2.38 ~AA5PPSS

Description: Set PowerOn Value and Safe Value.

Note: The command is for CB-7011/11D/11P/11PD only.

Syntax: ~AA5PPSS[CHK](cr)

~

delimiter character

AA

address of setting module (00 to FF)

5

command for setting PowerOn Value and Safe Value

PP

PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,

DO1off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SS

Safe Value, data format is same as PP

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example:

Command: ~0150003

Receive: !01

Set address 01 PowerOn Value is DO0 off, DO1 off, Safe

Value is DO0 on, DO1 on, return success.

Related Command:

Sec. 2.37 ~AA4

Related Topic:

Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation