28 @aarh – Measurement Computing CB-7011 User Manual
Page 50
50
CB-7011/CB-7011D, CD-7018 User’s Manual
2.28 @AARH
Description: Read High Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AARH[CHK](cr)
@
delimiter character
AA
address of reading module (00 to FF)
RH
command for reading high alarm
Response: Valid Command:
!AA(Data)[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command.
?
delimiter for invalid command.
AA
address of response module(00 to FF)
(Data)
high alarm value in engineer unit format.
Example:
Command: @01RH
Receive: !01+2.5000
Read address 01 high alarm, return +2.5000.
Related Command:
Sec. 2.24 @AAHI(Data)
Related Topic:
Sec. 3.6 High/Low Alarm