beautypg.com

3 #aa – Measurement Computing CB-7011 User Manual

Page 24

background image

24

CB-7011/CB-7011D, CD-7018 User’s Manual

2.3 #AA

Description: Read Analog Input

Syntax: #AA[CHK](cr)

#

delimiter character

AA

address of reading module(00 to FF)

Response:

Valid Command:

>(Data)[CHK](cr)

Syntax error or communication error may yield no re-

sponse.

>

delimiter for valid command

(Data)

analog input value, reference Sec. 1.10 for its format.

For CB-7018/18P, the data is the combination for each chan-

nel respectively.

Example:

Command: #01

Receive: >+02.635

Read address 01, return data success.

Command: #02

Receive: >4C53

Read address 02, return data in HEX format success.

Command: #04

Receive: >+05.123+04.153+07.234-02.356+10.000-

05.133+02.345+08.234

Module address 04 is CB-7018. Read address 04, get analog

input data of eight channels.

Related Command:

%AANNTTCCFF (Sec. 2.1), $AA2 (Sec. 2.7)

Related Topics:

Configuration Tables (Sec. 1.10)

This manual is related to the following products: