2.19 ~AAO(Data)

Description: Set Module Name

Syntax: ~AAO(Data)[CHK](cr)

~

delimiter character

AA

address of setting module (00 to FF)

O

command for setting module name

(Data)

new name for module, max 6 characters

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no

response.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example:

Command: ~01O7018

Receive: !01

Set address 01 module name to 7018, return success.

Command: $01M

Receive: !017018

Read address 01 module name, return 7018.