19 ~aao(data) – Measurement Computing CB-7011 User Manual
Page 40
40
CB-7011/CB-7011D, CD-7018 User’s Manual
2.19 ~AAO(Data)
Description: Set Module Name
Syntax: ~AAO(Data)[CHK](cr)
~
delimiter character
AA
address of setting module (00 to FF)
O
command for setting module name
(Data)
new name for module, max 6 characters
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no
response.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example:
Command: ~01O7018
Receive: !01
Set address 01 module name to 7018, return success.
Command: $01M
Receive: !017018
Read address 01 module name, return 7018.