20 ~aaev – Measurement Computing CB-7011 User Manual
Page 41
41
CB-7011/CB-7011D, CB-7018 User’s Manual
2.20 ~AAEV
Description: Enable/Disable Calibration
Syntax: ~AAEV[CHK](cr)
~
delimiter character
AA
address of setting module (00 to FF)
E
command for enable/disable calibration
V
1=enable calibration, 0=disable calibration
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no
response.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example:
Command: $010
Receive: ?01
Perform address 01 span calibration, return it is not ready for
calibration.
Command: ~01E1
Receive: !01
Set address 01 to enable calibration, return success.
Command: $010
Receive: !01
Preform address 01 span calibration, return success.
Related Command:
$AA0 (Sec. 2.5), $AA1 (Sec. 2.6)
Related Topic:
Calibration (Sec. 1.9)