CB-7011/CB-7011D, CB-7018 User’s Manual

2.2 #**

Description: Synchronized Sampling

Note: The command is for CB-7011/11D/11P/11PD only.

Syntax: #**[CHK](cr)

#

a delimiter character

**

synchronized sampling command

Response:

No response

Example:

Command: $014

Receive: ?01

Read synchronized sampling data, returns no valid data .

Command: #**

No response

Send synchronized sampling command.

Command: $014

Receive: >011+025.123

First read, get status=1, first read.

Command: $014

Receive: >010+025.123

Second read, get status=0, read verified.