24 @aahi(data) – Measurement Computing CB-7011 User Manual
Page 46
46
CB-7011/CB-7011D, CD-7018 User’s Manual
2.24 @AAHI(Data)
Description: Set High Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AADI[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
HI
command for setting high alarm value
(Data)
high alarm values, data format is in engineer unit format.
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example:
Command: @01HI+2.5000
Receive: !01
Set address 01 high alarm +2.5000, return success.
Related Command:
@AAEAT (Sec. 2.23), @AARH (Sec. 2.28)
Related Topic:
High/Low Alarm (Sec. 3.6)