CB-7011/CB-7011D, CB-7018 User’s Manual

2.6 $AA1

Description: Perform Zero Calibration

Syntax: $AA1[CHK](cr)

$

delimiter character

AA

address of setting module (00 to FF)

1

command for performing zero calibration

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command or the calibration is not

enabled

AA

address of response module(00 to FF)

Example:

Command: $011

Receive: !01

Perform address 01 zero calibration, return success.

Command: $021

Receive: ?02

Perform address 02 zero calibration, return the calibration is

not enabled before perform calibration command.

Related Command:

$AA0 (Sec. 2.5), ~AAEV (Sec. 2.20)

Related Topics:

Calibration (Sec. 1.9)