beautypg.com

22 @aado(data) – Measurement Computing CB-7011 User Manual

Page 44

background image

44

CB-7011/CB-7011D, CD-7018 User’s Manual

2.22 @AADO(Data)

Description: Set Digital Output

Note: The command is for CB-7011/11D/11P/11PD only.

Syntax: @AADI[CHK](cr)

@

delimiter character

AA

address of setting module (00 to FF)

DO

command for setting digital output

(Data)

output value, 00=DO0 off, DO1 off, 01=DO0 on, DO1

off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command. When the alarm is

enabled, the command will return invalid.

AA

address of response module(00 to FF)

Example:

Command: @01DO00

Receive: !01

Set address 01 digital output 00, return success.

Related Command:

@AADI (Sec. 2.21), @AAEAT (Set. 2.23), @AADA (Sec. 2.26)

Related Topic:

Sec. 3.5 Digital Output

This manual is related to the following products: