7 $aa2 – Measurement Computing CB-7011 User Manual
Page 28
28
CB-7011/CB-7011D, CD-7018 User’s Manual
2.7 $AA2
Description: Read Configuration
Syntax: $AA2[CHK](cr)
$
delimiter character
AA
address of reading module (00 to FF)
2
command for reading configuration
Response:
Valid Command:
!AATTCCFF[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
TT
type code of module (reference Sec. 1.10)
CC
baudrate code of module (reference Sec. 1.10)
FF
data format of module (reference Sec. 1.10)
Example:
Command: $012
Receive: !01050600
Read address 01 configuration, return success.
Command: $022
Receive: !02030602
Read address 02 configuration, return success.
Related Command:
%AANNTTCCFF (Sec. 2.1)
Related Topics: