Evolution Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards to the
following conditions:
The 6STC Poke-Thru Stem with the 6CTC or 6CT Service Head Fitting, and the 6ATCP, 6ATP, 6ATCPAV 6ATPAV, 6ATC or
6AT factory assembled Poke-Thru devices are for use with 1-, 1 1/2 -, or 2- hour rated unprotected reinforced concrete floors and
1-, 1 1/2 -, or 2- hour rated floors employing unprotected steel floor units and concrete topping (D900 Series Designs), or concrete
floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling
area below the Poke-Thru fittings).
The assembled Poke-Thru stem and service fitting will not reduce the ratings of the floor assembly when the thickness and type of
concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified:
1. Spacing – Minimum of 2' [610mm] OC and not more than one unit per 65 sq. ft. [6 sq. m] of floor area in each span.
2. Concrete – Minimum thickness of structural concrete topping of 2 1/4" [57mm] over metal deck or a minimum 3" [76mm]
thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.
3. Installation – Mounted in a 6" [152mm] diameter hole in concrete per installation instructions accompanying the fittings.
For use with power circuits, data and/or audio/visual cables as tabulated below:
The “TC” suffix letters indicate that the device may be installed on tile or carpet covered concrete floors. The “T” suffix
letter indicates that the device is intended to be installed on a concrete floor, embedded into the tile covering.
Max Copper
.0154 sq. in.
.0387 sq. in.
X-Section
[9.9
mm
2
]
[24.97
mm
2
]
Max #
(3) 12 AWG
(12) 14 AWG
Conductors
OUTER
CENTER
CHANNELS
CHANNEL
COPPER CROSS-SECTION
Size
Solid
#24
.00032 sq. in. [.20645mm
2
]
#22
.00050 sq. in. [.32258mm
2
]
#14
.00323 sq. in. [2.08386mm
2
]
#12
.00512 sq. in. [3.30321mm
2
]
#10
.00815 sq. in. [5.25805mm
2
]
#8
.01296 sq. in. [8.36127mm
2
]
Copper Cross Sectional Area
of Commonly Used Conductors
NOTE: Use above values for solid or stranded conductors.
NOTE:
When using conductor sizes other than listed above, the aggregate cross-sectional area of
the copper conductors shall not exceed the cross-sectional areas listed.
CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring.
Contact manufacturer for replacement. Field modifications will void UL Listing
and Classification. Replacement receptacle is limited to this manufacturers'
Catalog No 68REC.
- 68REC-25 6PPS 8 5PTHA 575CHA 175CHA-LJB 1BHA 152CHA 1BLH 175CHA 5BLH 1PTHA 1125CHA 15FFHA 682A 682A-PT 6S2 6ACT8A 6TRAC 6MAAP2A 6MOSBS 6DEC 6DP 6MOS 6B 6AAP 68B 6SER 6MAAP 6S1 68MAAP 6ATCFFBK 6ATCFFGY 6ATCFFNK 6ATCFFBS 6ATCFFBZ 880ADP FITFIT Multi-Service Poke-Thru Device Abandonments AP-FITTCFIT Multi-Service Poke-Thru Device Abandonments 221-21CARPET FIT Multi-Service Poke-Thru Device Abandonments 221-21TILE FIT Multi-Service Poke-Thru Device Abandonments RC9-PPT RCAPFFTCBK RC9AFFTC v.1 6ATC 8AT 6PPS