For carpet or surface mounted tile – Legrand 68REC User Manual

Page 2

background image

CONVENTIONAL WIRING SCHEMATIC

ISOLATED GROUND WIRING SCHEMATIC

BLACK or HOT

BLACK

BLACK or HOT

BLACK

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

WHITE or NEUTRAL

WHITE

WHITE or NEUTRAL WHITE

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

GREEN or GROUND

GREEN

ISOLATED GROUND GREEN

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

System Ground

GREEN or GROUND GREEN

(jumper wire)

From branch circuit

from Poke-Thru

System Ground

junction box

2

Step 3

Place appropriate gasket
around poke thru and
slide under flange. Use flat
foam gasket for surface
tile applications or use
round neoprene gasket for
carpet applications. For
the flush tile applications
no gasket is needed.

Step 1 Attach data and AV plates and wire power and data devices (Can be completed above floor).

Refer to wiring schematic below for power wiring options.

INSTALLING COMPLETE ASSEMBLY

Catalog Nos. 6ATCP, 6ATP

Catalog Nos. 6ATCPAV, 6ATPAV

WARNING: Ground wire from junction box must be connected to system ground.
CAUTION: Receptacle mounting means not grounded. Grounding wire connection required. For isolated

ground wiring, connect ground leads to a separate isolated grounding conductor. See NEC 250-
146(d).

If necessary remove Feed Plates to pull communications wires through Poke-Thru device.
Replace Feed Plates when finished pulling wires.

Catalog Nos. 6ATCP, 6ATP

Catalog Nos. 6ATCPAV, 6ATPAV

CAUTION: To maintain fire classification, Feed Plates must be installed.

For Carpet or surface mounted tile

GREEN (jumper wire)
from Poke-Thru
junction box

Circuit A Wiring

Catalog Nos. 6ATCP, 6ATCPAV

Circuit B Wiring

Catalog Nos. 6ATCP only

CONVENTIONAL WIRING SCHEMATIC

ISOLATED GROUND WIRING SCHEMATIC

BLACK or HOT

RED

BLACK or HOT

RED

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

WHITE or NEUTRAL

WHITE W/ BLUE STRIPE

WHITE or NEUTRAL

WHITE W/ BLUE STRIPE

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

GREEN or GROUND

GREEN W/ YELLOW STRIPE

ISOLATED GROUND

GREEN W/ YELLOW STRIPE

From branch circuit

from Poke-Thru receptacle

From branch circuit

from Poke-Thru receptacle

System Ground

GREEN or GROUND

GREEN (jumper wire)

From branch circuit

from Poke-Thru

System Ground

junction box

GREEN (jumper wire)
from Poke-Thru
junction box

Step 2 If circuit is connected

to an isolated ground,
apply IG icon on
receptacle plate
as shown.

NOTE: The orange triangle shall only be placed

on devices that are wired for isolated
ground. See NEC 250-146(d).