Legrand AL5200 Series Large Multi-Channel Aluminum Surface Raceway User Manual
Al5200 aluminum surface raceway, Installation instructions
AL5200 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATION
CAPACITY CROSS SECTIONAL AREA
CABLE/WIRE SIZE
OD
8.5" [216mm]
4.85" [122mm]
3.78" [89mm]
3.86" [99mm]
4.36" [114mm]
Inches
[mm]
20%*
40%**
20%*
40%**
20%*
40%**
20%*
40%**
20%*
40%**
UNSHIELDED
4-pair, 24 AWG,cat.3
0.190
[4.8]
60
20
34
68
26
53
27
54
30
61
TWISTED PAIR
4-pair, 24 AWG,cat.4
0.220
[5.6]
44
89
25
51
19
39
20
40
22
45
4-pair, 24 AWG,cat.5
0.250
[6.3]
34
69
19
39
15
30
17
31
17
35
TELEPHONE
2-pair, 24 AWG
0.140
[3.6]
10
221
63
126
49
98
50
100
56
113
3-pair, 24 AWG
0.150
[3.8]
96
193
54
109
42
85
43
87
49
98
4-pair, 24 AWG
0.190
[4.8]
60
120
34
68
26
53
27
54
30
61
25-pair, 24 AWG
0.410
[10.4]
12
125
7
14
5
11
5
11
6
13
COAXIAL
RG58/U
0.195
[5.0]
57
114
32
64
25
50
25
51
29
58
RG59/U
0.242
[6.1]
37
74
21
42
16
32
16
33
18
37
RG62/U
0.242
[6.1]
37
74
21
42
16
32
16
33
18
37
RG6/U
0.270
[6.9]
29
59
16
33
13
26
13
26
15
30
TWINAXIAL
100 Ohm
0.330
[8.4]
19
39
11
22
8
17
9
18
10
20
SHIELDED
TYPE 1
0.390
[9.9]
14
28
8
16
6
12
6
12
7
14
TWISTED PAIR
TYPE 2
0.465
[11.8]
10
20
5
11
4
8
4
9
5
10
TYPE3
0.245
[6.2]
36
72
20
41
20
32
16
32
18
36
FIBER OPTIC
Two Standard(Duplex)
Multimode, 62.5/125um
0.190
[4.8]
60
120
34
68
26
53
27
54
30
61
AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH OUT DEVICE
WIRE TYPE
2.4" [61mm]
2.85" [72mm]
3.5" [85mm]
3.9" [99mm]
4.5" [114mm]
4.8" [122mm]
8.5" [216mm]
THWN/THHN
#6
18
22
27
30
34
37
65
#8
25
30
37
42
48
51
91
#10
52
62
76
84
98
104
184
#12
82
97
119
113
154
164
290
#14
110
131
161
179
207
220
391
AL5200 Aluminum
Surface Raceway
INSTALLATION INSTRUCTIONS
AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH DUPLEX DEVICE (1.34 Sq.in.)
WIRE TYPE
3.78" [89mm]
3.86" [99mm]
4.36" [114mm]
4.85" [122mm]
8.5" [216mm]
THWN/THHN
#6
16
19
24
26
55
#8
23 27
34
37
76
#10
47
55
68
75
155
#12
74
87
108
118
244
#14
99
117
145
159
329
NOTE: * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
8.5 sq. in.
[215.90mm]
5"
[127mm]
2 3/4"
[70mm]
2 3/16"
[56mm]
2"
[51mm]
4.86 sq. in.
[123.19mm]
3.78 sq. in.
[96.01mm]
3.90 sq. in.
[99.06mm]
4.50 sq. in.
[114.30mm]