AL2000 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATION

OD

CABLE/WIRE SIZE

[In.]

[mm]

20% FILL*

40% FILL**

UNSHELDED

4-pair, 24 AWG, Cat 5

0.220

[5.6]

5

11

TWISTED PAIR

4-pair, 24 AWG, Cat, 3

0.190

[4.8]

7

15

TELEPHONE

2-pair, 24 AWG

0.140

[3.6]

14

28

3-pair, 24 AWG

0.150

[3.8]

12

25

4-pair, 24 AWG

0.190

[4.8]

7

15

25-pair, 24 AWG

0.410

[10.4]

1

3

COAXIAL

RG58/U

0.195

[5.0]

7

14

RG59/U

0.242

[6.1]

4

9

RG62/U

0.242

[6.1]

4

9

RG6/U

0.270

[6.9]

3

7

TWINAXIAL

100 Ohm

0.330

[8.4]

2

5

SHELDED

Type 1

0.390

[9.9]

1

3

TWISTED PAIR

Type 2

0.465

[11.8]

1

2

Type 3

0.245

[6.2]

4

9

AL2000 Aluminum
Surface Raceway

INSTALLATION INSTRUCTIONS

AL2000 RACEWAY WIRE FILL CAPACITIES FOR POWER

WIRE TYPE

TW

THW

RHH/RHW

THHN/THWN

POWER WIRING

6 AWG

5

5

4

8

WITHOUT DEVICE

8 AWG

9

7

5

12

1.1 sq. in. cross section

10 AWG

20

14

10

24

12 AWG

26

17

16

38

14 AWG

33

21

19

51

POWER WIRING AWG

6 AWG

3

2

2

3

WITH DEVICE

8AWG

4

3

2

6

515 amp devices

10 AWG

5

3

3

8

.8 sq. in. cross section

NOTE: * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict

cross sectional area.

** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.

Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.

All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.

Note: Raceway may be configured in single or multiple channels

to accommodate power or communications wiring.

MAXIMUM CROSS SECTION

1.1 sq. in.

[27mm]

1 7/16"

[37mm]

1 1/8"

[29mm]

.8 sq. in.