INSTALLATION
3-38
HySpeed HSD130 RHF
Instruction Manual
Line disconnect switch
The line disconnect switch serves as the supply-voltage disconnecting (isolating) device. Install
this switch near the power supply for easy access by the operator.
Installation must be performed by a licensed electrician and according to applicable national
and local codes.
The switch should:
•
isolate the electrical equipment and disconnect all live conductors from the supply
voltage when in the “OFF” position
• have one “OFF” and one “ON” position clearly marked with “O” (OFF) and “l” (ON)
•
have an external operating handle capable of being locked in the “OFF” position
• contain a power-operated mechanism that serves as an emergency stop
• have slow-blow fuses installed for the proper breaking capacity (see table above).
Power cable
Cable sizes vary based on the distance of the receptacle from the main box. Use a 4-conductor Type SO input power
cable with a conductor temperature rating of 60° C (140° F). Installation must be performed by a licensed electrician.
9
Power requirements
General
All switches, slow-blow fuses and power cables are customer-supplied and must be
chosen as outlined by applicable national and local electrical-codes. Installation must be
performed by a licensed electrician. Use a separate primary-line disconnect switch for
the power supply.
FUSE
SWITCH BOX
Note:
Cable AWG recommendations taken from table 310-16 of the National Electric Code handbook (USA).
Recommended cable size
for 15 m (50 feet)
Input
Rated input current
Recommended
maximum length
voltage
Phase
@ 19.5 kW output
slow-blow fuse size
Rated for 60° C
200/208 VAC
3
62/58 amps
85 amps
30 mm
2
(3 AWG)
220 VAC
3
56 amps
80 amps
30 mm
2
(3 AWG)
240 VAC
3
52 amps
65 amps
26 mm
2
(4 AWG)
400 VAC
3
32 amps
40 amps
10 mm
2
(8 AWG)
440 VAC
3
28 amps
35 amps
8 mm
2
(8 AWG)
480 VAC
3
26 amps
35 amps
8 mm
2
(8 AWG)
600 VAC
3
21 amps
30 amps
6 mm
2
(10 AWG)