SERVICE CLEARANCES / ACCESS PANEL LOCATIONS FOR MODEL ERCH
Clearances must be maintained on all
sides of this unit . This especially is true
with the top of this unit . Hot air is being
discharged through the condensing
fans during operation, and the more
clearance available, the better the
chance of avoiding recirculation or coil
starvation . This unit should never be
placed under an overhang or inside a
building . A minimum of 48 inches over
the condensing fans is recommended .
ERCH-20, 45, 55, and 90 units require
minimum clearances for access on all sides for routine maintenance . Filter replacement, drain pan inspection
and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples of
routine maintenance that must be performed . Blower and motor assemblies, energy recovery wheel cassette,
coil and filter sections are always provided with a service door or panel for proper component access .
Clearances for component removal may be greater than the service clearances, refer to drawings for these
dimensions .
ERCH-20
ERCH-45
ERCH-55
ERCH-90
Clearances for service and component removal on ERCH-20 and ERCH-45
* Clearance for energy wheel removal on ERCH-20
** Clearance for energy wheel removal on ERCH-45
Clearances for service and component removal on ERCH-55 and ERCH-90
WHEEL CASSETTE
COIL
SECTION
ACCESS P
ANEL
ACCESS P
ANEL
ACCESS PANEL
ACCESS P
ANEL
ACCESS PANEL
ACCESS P
ANEL
ACCESS PANEL
EXHAUST
HOOD
OUTDOOR AI
R
HOOD
INTAKE
EXHAUST AIR
ELECTRICAL BOX
FIL
TER
S
FIL
TER
S
ACCESS PANEL
IG HEA
TER
36 IN
36 IN
12 IN
*48 IN
**64 IN
52 IN
CLEARANCE
WITH IG HEATER
MINIMUM
WHEEL CASSETTE
COIL
SECTION
ACCESS
PA
NE
L
ACCESS P
ANEL
ACCESS PANEL
ACCESS P
ANEL
ACCESS PANEL
ACCESS
PA
NE
L
ACCESS PANEL
EXHAUST
HOOD
OUTDOOR AI
R
HOO
D
INTAKE
EXHAUST AIR
ELECTRICAL BOX
FIL
TERS
FIL
TERS
ACCESS PANEL
IG HEA
TER
42 IN
42 IN
12 IN
42 IN
52 IN
CLEARANCE
WITH IG HEATER
MINIMUM
Minimum 12 inches
clearance
Condensing Coil Intake
Keep this area clear
Minimum 48 inches
clearance