Troubleshooting - general refrigeration circuit – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual

Page 50

background image

50

Energy Recovery Unit with Packaged DX

Symptom

Possible Cause

Corrective Action

Liquid line

is too hot

Refrigerant undercharge .

Adjust the charge by subcooling .

High discharge pressure .

See “High discharge pressure” .

Liquid line is

frosted or wet

Restriction in liquid line .

Clear restriction upstream of point of frosting .

Suction line

is frosting

Insufficient evaporator airflow .

Check airflow, check filters, check drive for
loose parts or belts .

Restriction in suction or liquid line .

Restriction upstream of point of frosting .

Malfunctioning or defective expansion valve .

Check bulb of thermal expansion valve .

Frost on evap coil

Hot gas bypass valve not functioning properly .

Check valve . If defective, replace .

Manual hot gas bypass valve closed .

Open valve .

Troubleshooting - General Refrigeration Circuit

Always have a completed Pre-Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.