beautypg.com

Optional accessories, Remote control panel and wiring schematics – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual

Page 20

background image

20

Energy Recovery Unit with Packaged DX

OPTIONAL ACCESSORIES

G

C

R

7-Day Timer or On/Off Switch

The remote panel is available with a number of different
alarm lights and switches to control the unit . The remote
panel ships loose and requires mounting and wiring in
the field .

The remote panel is available with the following options:

• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
• Wheel rotation sensor light

S1 - Unit On/Off

Refer to Electrical Connections section for Field Control Wiring recommendations.

Remote Control Panel and Wiring Schematics

7-Day Timer

Terminal Block

in

Unit Control

Center

For 7-Day Timer, use blue and black wires .
Red wires should be capped off .

G

C

R

Hand/Off/Auto Switch

Terminal Block

in

Unit Control

Center

Hand/Off/Auto Switch allows the unit to
“Off” - off
“On” - Manual Operation
“Auto” - Unit is controlled by BMS, RTU, etc .

NOTE: RTU controllers are by others .

On

Off

BMS

Auto