Troubleshooting - General Refrigeration Circuit

Symptom

Possible Cause

Corrective Action

Low suction

pressure

Refrigerant undercharge .

Check pressures and subcooling .

Blower running backward .

Interchange any two wires from 3 phase
disconnect .

Loose blower, pulley or belts .

Check drive pulley alignment, belt tension .

Low entering air temperature (low load
condition) .

Check entering air wet bulb conditions .

Refrigerant leak .

Check system for leaks . Repair leaks and add
refrigerant .

Evaporator dirty or iced up or airflow restricted .

Check defrost system . Clean the coil .
Check fan operation . Check airflow .

Plugged liquid line filter-drier .

Replace filter-drier .

Improper suction pressure regulator setting .

Check setting and correct as required .

Expansion valve defective, superheat too high,
or valve too small .

Adjust valve for proper superheat or replace the
expansion valve if too small or defective .

Moisture in system .

Reclaim refrigerant, check for leaks, recharge .

Low discharge

pressure

Insufficient refrigerant charge .

Check subcooling, check for leak . Repair leak
and add refrigerant .

Defective or improperly adjusted expansion
valve .

Check superheating and adjust thermal
expansion valve .

Low suction pressure .

See “Low suction pressure” .

Faulty condenser temperature controls .

Check condenser controls and reset to obtain
desired condensing temperature .

Compressor

short cycles

Thermostat location or malfunction .

Check thermostat, check heat anticipator
setting .

Improper refrigerant charge .

Check subcooling, verify superheat .

Defective high or low pressure control .

Check high or low pressure switch .

Liquid floodback .

Possible tight bearings, see above .

Defective expansion valve .

Check thermal expansion valve and superheat .

Poor air distribution .

Check ductwork for recirculating .

High discharge pressure .

See “High discharge pressure” .

Leaking discharge valves in compressor .

See “High suction pressure” .

Low airflow at evaporator(s) .

Check blower operation and airstream
restrictions .

Incorrect unit selection (oversized) .

Contact factory .

Always have a completed Pre-Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or