beautypg.com

Coil application recommendations, Water coils – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual

Page 11

background image

11

Energy Recovery Unit with Packaged DX

COIL APPLICATION RECOMMENDATIONS

Factory installed cooling and heating components are mounted
in the coil section of the unit . The coil section is downstream
of the energy wheel on the supply air side of the unit .

Note the coil connection locations on the picture . Coil
connections are located external to the unit as shown . Coil
connections that are not external have been ordered from the
factory with interior or exhaust airstream coil connections .

Note: DX coil liquid connection is internal to units .

WATER COILS

1 . Piping should be in accordance with accepted industry

standards . Pipework should be supported independently
of the coils . Water connections are male NPT iron pipe .
When installing couplings, do not apply undue stress to the
connection extending through the unit . Use a backup pipe wrench to avoid breaking the weld between coil
connection and header .

2 . Connect the WATER SUPPLy TO THE BOTTOM CONNECTION on the air leaving side and the WATER

RETURN TO THE TOP CONNECTION on the air entering side . To insure proper venting, an external air vent
in the piping is recommended . Connecting the supply and/or return in any other manner will result in very
poor performance . Be sure to replace factory installed grommets around coil connections if removed for
piping . Failure to replace grommets will result in water leakage into the unit and altered performance .

3 . The air vent at the uppermost point should be temporarily opened during system start-up to release all of the

air from the coil . To maintain heat transfer capacity, periodically vent any air in coil .

4 . Water coils are not normally recommended for use with entering air temperatures below 40ºF; however,

the energy recovery wheel maintains a pre-coil temperature higher than 40ºF . No control system can be
depended on to be 100% safe against freeze-up with water coils . Glycol solutions or brines are the only safe
media for operation of water coils with low entering air conditions .

CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLy RECOMMENDED .

5 . Pipe sizes for the system must be selected on the basis of the head (pressure) available from the circulation

pump . The velocity should not exceed 6 feet per second and the friction loss should be approximately 3 feet
of water column per 100 feet of pipe .

DIRECT EXPANSION (DX) COILS WITH INTEGRAL CONDENSING SECTION

1 . The condensate drain pipe should be sized adequately to ensure the condensate drains properly . Refer to

Drain Trap section .

Hot

water coil

connections

Coil access door