Optional accessories, Economizer application/operation – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual
Page 15

15
Energy Recovery Unit with Packaged DX
The energy recovery wheel operation can be altered to take advantage of economizer operation (free cooling) .
Two modes are available: 1) De-energizing the wheel or 2) Modulating the wheel . A field supplied call for cool
(y1) is required .
De-energizing the wheel is accomplished with a signal from a Temperature or Enthalpy sensor mounted
in the air intake compartment . This Primary sensor will de-energize the energy wheel when the outdoor air
temperature (factory default is 65ºF) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable
set point . An Override temperature sensor is also furnished in the outdoor air intake compartment to deactivate
economizer mode . The Override (with field adjustable set point) is set at some temperature lower than the
Primary sensor (factory default is 50ºF) . Effectively, the two sensors create a deadband where the energy
recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned .
Testing
Temperature Sensor with Override
• Turn both Temperature and Override thermostats down as low as they go. The
wheel should be rotating .
• Turn the Temperature sensor up as high as it goes, and keep the Override
sensor as low as it will go . The wheel should stop rotating .
• Turn both sensors as high as they will go. The wheel should start rotating.
• Set the Temperature sensor at desired point for economizer operation to begin.
Set the Override sensor at desired point for economizer operation to end
(factory default is 65ºF and 50ºF, respectively) .
Enthalpy Sensor with Override
• Turn unit power off. Disconnect C7400 solid state enthalpy sensor from terminal
So on the enthalpy controller . Also, disconnect the 620 ohm resistor from
terminal Sr on the enthalpy controller . Turn unit power on . The LED on the
enthalpy controller should light and the energy recovery wheel should not rotate .
• Turn unit power off. Reconnect 620 ohm resistor to terminal Sr on the enthalpy
controller . Turn unit power on . The LED on the enthalpy controller should not
light and the energy recovery wheel should energize and rotate .
If the steps above provide the results described, the enthalpy economizer is
working properly .
• Turn unit power off. Reconnect C7400 solid state enthalpy sensor
to terminal So .
Modulating the Wheel
In applications in which an internal heat gain is present in the space,
the rotational speed of the energy wheel may be modulated (via
variable frequency drive) to avoid overheating the space during the
winter . The speed of the energy wheel will be controlled in response to
the discharge temperature set point .
Sequence of Operation:
The variable frequency drive is fully programmed at the factory (refer to VFD section
for more information) . A “call for cool” must be field wired to the unit (terminals provided in unit - refer to wiring
diagram in unit control center) to allow for initiation of economizer mode . When the space calls for cooling,
factory supplied controls will drive the following wheel operations:
T
OA
> T
RA
: Wheel runs at full speed (maximum energy recovery)
T
OA
< T
RA
and T
OA
> T
SA
: Wheel is stopped (no energy recovery)
T
OA
< T
RA
and T
OA
< T
SA
: Wheel will modulate to maintain discharge temperature
where (T
OA
) is the outdoor air temperature set point, (T
RA
) is the return air temperature set point, and (T
SA
) is the
supply air discharge thermostat set point .
Economizer Application/Operation
Temperature Sensor
with Override
Enthalpy Sensor
with Override
Enthalpy
Controller
OPTIONAL ACCESSORIES