beautypg.com

Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual

Page 5

background image

5

Energy Recovery Unit with Packaged DX

Rooftop units require curbs to be mounted first . The duct
connections must be located so they will be clear of structural
members of the building .
1. Factory Supplied Roof Curbs

Roof curbs are Model GKD, which are shipped in a knockdown
kit (includes duct adapter) and require field assembly (by others) .
Assembly instructions are included with the curb .

2. Install Curb

Locate curb over roof opening and fasten in place . (Refer
to Recommended Roof Openings) . Check that the diagonal
dimensions are within ±1/8 inch of each other and adjust as
necessary . For proper coil drainage and unit operation, it is
important that the installation be level . Shim as required to level .

3. Install Ductwork

Installation of all ducts should be done in accordance with
SMACNA and AMCA guidelines . Duct adapter provided to support
ducts prior to setting the unit .

4. Set the Unit

Lift unit to a point directly above the curb and duct openings .
Guide unit while lowering to align with duct openings . Roof curbs
fit inside the unit base . Make sure the unit is properly seated on
the curb and is level .

All dimensions shown are in inches . Weights are for 12 inch high curbs .

Curb Outside Dimensions

Roof curb details, including

duct location dimensions, are

available on ERCH roof curb

assembly instructions,

Part #468280.

Curb Outside Dimensions and Curb Weights (lbs)

Model

L

W

Weight

ERCH-20

104 .88

51

310

ERCH-45

115 .75

60 .63

400

ERCH-55

129 .88

71 .5

510

ERCH-90

148 .13

90 .75

720

ROOF CURB MOUNTING

INSTALLATION CONCERNS

Unobstructed airflow to the condensing section must be maintained at all times to ensure proper operating

efficiency and capacity of the cooling system . Unit placement should allow proper airflow over the condensing

section . The unit may not operate properly and damage may occur to the system if there is coil starvation (lack of

air over condenser) or warm air recirculating back through the condensing coil . Recirculating air is caused when

the unit is placed near obstacles that can redirect exhaust air from the condensing fans, back around to the coil

inlet . Overhangs or walls near the condensing section are two examples .
Another consideration when placing the unit is prevailing wind direction . The condensing coil operation can be

significantly affected when winds are blowing continuously and directly at the condensing coil . On hot days, the

wind will help the system by providing extra flow over the coil . But on cooler days, that same wind may overcool

the refrigerant, and cause hot gas bypass to operate more frequently, causing higher operating costs . Therefore,

avoiding direct winds will provide a more stable operation of the system throughout the cooling season .
Lack of air over the coil can reduce efficiencies and affect system operation . Do not allow debris (such as leaves

and trash), to accumulate on or near the unit . Keeping debris clear of the unit will ensure minimal obstruction to

the coils, keeping efficiencies and operation closer to design . The unit typically should not operate when snow

is present . In the event this is possible, make sure all snow is clear of the coil and condensing fans prior to

operating the unit .
If more than one unit is being installed, make provisions so discharge air from either the condensing fans or

exhaust fan of the unit do not discharge towards another unit’s intake . Also, OA intake and condensing sections

should be spaced as too allow proper airflow to each unit helping ensure the units operate as intended .
When cutting only duct openings, cut opening 1 inch (25mm) larger than duct size to allow clearance for

installation . Area enclosed by roof curb must comply with clearance to combustible materials . If the roof is

constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with

non-combustible material which has an “R” value of at least 5 . If area within curb is open, higher radiated sound

levels may result .
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be maintained

between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A .