Troubleshooting - general refrigeration circuit – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual
Page 49
49
Energy Recovery Unit with Packaged DX
Troubleshooting - General Refrigeration Circuit
Symptom
Possible Cause
Corrective Action
Low or no
oil pressure
Low oil level (trapped oil in evaporator or
suction line) .
Thoroughly defrost evaporator . After defrost,
observe level, add oil . Check for leaks . Check
lines for proper slope and traps .
Excessive liquid refrigerant in the crankcase .
Adjust expansion valve for higher superheat .
Check crankcase heater .
Worn oil pump .
Replace the oil pump .
Worn compressor bearings .
Replace the compressor .
Loose fitting on oil line or pump housing gasket
leaking . (R22 only)
Check and tighten system . Check bottom plate
or compressor .
Compressor short cycling .
Check low pressure control setting .
Compressor
loses oil
Refrigerant leak .
Check system for leaks . Repair leaks and add
refrigerant .
Short cycling .
Check low pressure control settings .
Refrigerant flood back .
Check thermal expansion valve setting . Check
for refrigerant overcharge .
Improper piping or traps .
Verify proper piping slopes .
Running cycle is
too long or unit
operates
continuously
Refrigeration undercharged .
Check subcooling .
Dirty filter or evaporator coil .
Check filter, coil and airflow .
Dirty or clogged condenser coil .
Check coil and airflow .
Air or other non-condensables in system .
Check equalized high side pressure with
equivalent outdoor temperature .
Defective compressor .
See “High suction pressure” .
Restriction in suction and liquid line .
Check for restrictions in refrigerant circuit .
Control contacts stuck .
Check wiring .
Excessive load .
Add more equipment or reduce room load .
Too low of a system thermostat setting or
defective thermostat .
Adjust or replace thermostat .
Always have a completed Pre-Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.