Energy Recovery Unit with Packaged DX

INSTALLATION

The system design and installation should follow accepted industry
practice, such as described in the ASHRAE Handbook .
Adequate space should be left around the unit for piping coils and drains,
filter replacement, and maintenance . Sufficient space should be provided
on the side of the unit for routine service and component removal should
that become necessary .
See Service Clearances/Access Panel Locations section for more details .

LIFTING

1) Before lifting, be sure that all shipping material has been

removed from unit .

2) To assist in determining rigging requirements, weights are

shown below .

3) Unit must be lifted by all lifting lugs provided on base

structure .

4) Rigger to use suitable mating hardware to attach to unit

lifting lugs .

5) Spreader bar(s) must span the unit to prevent damage to

the cabinet by the lift cables .

6) Always test-lift the unit to check for proper balance and

rigging before hoisting to desired location .

7) Never lift units by weatherhoods .
8) Never lift units in windy conditions .
9) Preparation of curb and roof openings should be completed

prior to lifting unit to the roof .

10) Check to be sure that gasketing (supplied by others) has

been applied to the curb prior to lifting the unit and setting
on curb .

11) Do not use fork lifts for handling unit .

Lift using lifting lugs

and spreader bar

UNIT WEIGHTS & RECOMMENDED ROOF OPENING

SUPPLY

DISCHARGE

EXHAUST

INTAKE

U

V

1/2 inch

1/2 inch

SAFETY WARNING

All factory provided lifting

lugs must be used when

lifting the units . Failure to

comply with this safety

precaution could result in

property damage, serious

injury, or death .

Unit weights assume rooftop configuration with weatherhoods, filters,
outdoor air damper, six row DX coil, integral condensing section and
an indirect gas fired furnace .

Unit

Size

Approximate

Weight (lbs)

U

(inches)

V

(inches)

ERCH-20

2150

46

46

ERCH-45

3500

54

48

ERCH-55

4450

65

58

ERCH-90

6200

85

63

CAUTION!

Unit is designed for Outdoor installation only . Follow all guidelines in this manual for proper installation .

HANDLING

While this unit was constructed with quality and dependability in mind, damage still may occur during
handling of the unit for installation . Exercise extreme caution to prevent any damage from occurring to the
refrigerant system . This unit contains a system pressurized with refrigerant that if damaged, could leak into
the atmosphere or cause bodily harm due to the extreme cold nature of expanding refrigerant . Use protective
equipment such as gloves and safety glasses to minimize or prevent injury in case of a system leak during
installation .

Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the
corresponding ductwork . Be sure to allow for the recommended service clearances when positioning opening
(see Service Clearances) . Do not face the outdoor air intake of the unit into prevailing wind and keep the intake
away from any other exhaust fans . Likewise, position the exhaust discharge opening away from outdoor air
intakes of any other equipment .