Start-up checklist for unit – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual
Page 26
26
Energy Recovery Unit with Packaged DX
Line Voltage - check at unit disconnect
L1-L2
________ Volts
L2-L3 ________ Volts
L1-L3 _______ Volts
Motor Amp Draw:
Supply Motor Amps
L1
________ Amps L2
________ Amps
L3 ________ Amps
Exhaust Motor Amps
L1
________ Amps L2
________ Amps
L3 ________ Amps
Fan RPM:
Supply Fan RPM _____________
Exhaust Fan RPM _____________
Correct fan rotation direction:
Supply Fan
yes / No
Exhaust Fan
yes / No
Energy Wheel Motor:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Compressor 1:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Crankcase Heater
________ Amps
Compressor 2:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Crankcase Heater
________ Amps
Condensing Fan 1:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Condensing Fan 2:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Condensing Fan 3:
L1
________ Amps L2
________ Amps
L3 ________ Amps
Outdoor Air Temperature
________ Deg F
Return Air Temperature
________ Deg F
Outdoor Air Relative Humidity
________ % RH
Return Air Relative Humidity
________ % RH
Superheat
________ Deg F
Should be between 8º and 12ºF
Subcooling
________ Deg F
Should be between 12º and 17ºF
Discharge Pressure
PSIG
Should be between 200 and 280 PSIG for R22
or 300 and 500 PSIG for R410a
Suction Line Pressure
PSIG
Should be between 60 and 80 PSIG for R22
or 100 and 135 PSIG for R410a
Liquid Line Temp
________ Deg F
Suction Line Temp
________ Deg F
Moisture Indicating Sight Glass
Liquid Visible
yes / No
Color of Center Dot
Green / yellow
Hot Gas Bypass Operational
yes / No
START-UP CHECKLIST FOR UNIT