Start-up checklist for unit – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual

Page 26

background image

26

Energy Recovery Unit with Packaged DX

Line Voltage - check at unit disconnect

L1-L2

________ Volts

L2-L3 ________ Volts

L1-L3 _______ Volts

Motor Amp Draw:

Supply Motor Amps

L1

________ Amps L2

________ Amps

L3 ________ Amps

Exhaust Motor Amps

L1

________ Amps L2

________ Amps

L3 ________ Amps

Fan RPM:

Supply Fan RPM _____________

Exhaust Fan RPM _____________

Correct fan rotation direction:

Supply Fan

yes / No

Exhaust Fan

yes / No

Energy Wheel Motor:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Compressor 1:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Crankcase Heater

________ Amps

Compressor 2:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Crankcase Heater

________ Amps


Condensing Fan 1:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Condensing Fan 2:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Condensing Fan 3:

L1

________ Amps L2

________ Amps

L3 ________ Amps

Outdoor Air Temperature

________ Deg F

Return Air Temperature

________ Deg F

Outdoor Air Relative Humidity

________ % RH

Return Air Relative Humidity

________ % RH

Superheat

________ Deg F

Should be between 8º and 12ºF

Subcooling

________ Deg F

Should be between 12º and 17ºF

Discharge Pressure

PSIG

Should be between 200 and 280 PSIG for R22

or 300 and 500 PSIG for R410a

Suction Line Pressure

PSIG

Should be between 60 and 80 PSIG for R22

or 100 and 135 PSIG for R410a

Liquid Line Temp

________ Deg F

Suction Line Temp

________ Deg F

Moisture Indicating Sight Glass

Liquid Visible

yes / No

Color of Center Dot

Green / yellow

Hot Gas Bypass Operational

yes / No

START-UP CHECKLIST FOR UNIT