OPERATING SEQUENCE
The exact sequence of events that occurs during the operation of the pump is determined by
various switch settings, inputs, and the user. A typical transaction is explained below.
1.
Turn on the pump handle. If AC is present on the Pump Motor Feed line, the reset cycle
begins. The display:
•
goes blank for one second
•
shows all 8's for one second
•
goes to 0.000 (gallons) or 0.00 (liters) and remains for one second.
The pump motor turns on. If equipped, the slow flow valve turns on.
2.
The user begins to dispense fuel. Quantity will not be recorded on the display until 0.010
gallons (0.04 liters) are reached, however, all pulses will be sent out on the Pulse Output line,
if equipped. At 0.010 gallons (0.04 liters), the fast flow valve turns on, if equipped.
3.
The pump continues to run until one of the following conditions occurs. These conditions turn
off all relays.
•
The handle is turned off.
•
The Pump Motor Feed line is turned off.
•
A pulser error is detected.
•
A timeout of 255 seconds is reached. If connected to a fuel management system, the
timeout loaded into the system will be used.
•
A quantity of 990.000 gallons (9900.00 liters) is reached. If connected to a fuel
management system, the limit set in the system will be used.
•
The pump is halted by an operator of a fuel management system.
•
An AC power failure occurs.
4.
The 9820A continues to monitor for pulses until a 2 second period with no pulses occurs. At
this time the transaction is considered completed.