Jp2 - mode, Jp3, jp4 - leak detect delay, Jp5 - hose pressurization – Gasboy 9800 Atlas User Manual
Page 12: Jp6 - authorization
![background image](https://www.manualsdir.com/files/787313/content/doc012.png)
Installing Atlas 9800 CPU Board (M06333KXXXX)
Page 12
MDE-4652D Atlas™ 9800 Electronics Field Installation Instructions · April 2013
JP2 - Mode
This jumper selects the mode in which the pump/dispenser operates. Set the mode to “Online”
if the pump/dispenser communicates to a controlling system (for example, Gasboy TopKAT
™
or CFN System). Set the mode to “Standalone” for all other configurations (for example,
Gasboy Series 1000 Fuel Management System or no controlling system).
Mode
JP2
Standalone Jumpered
Online
Open
JP3, JP4 - Leak Detect Delay
These jumpers select the delay time used by leak detectors in Submersible Turbine Pump
(STP) applications. The delay time is the period between the activation of the submersible
pump and the activation of the slow flow valve. The delay time must be set according to the
type of leak detector installed on the STP to allow for a normal leak test for each transaction.
The delay time must be set to 0 seconds for suction pumps.
Delay Time JP3
JP4
0 seconds
Jumpered
Jumpered
4 seconds
Jumpered
Open
5 seconds
Open
Jumpered
6 seconds
Open
Open
JP5 - Hose Pressurization
For US Gallons (always in Hose Pressurization mode), this jumper is ignored. This jumper is
used to determine if hose pressurization is used. If enabled, the slow flow valve is opened
before reset is complete, to allow the hose to be pressurized before fuel dispensing begins.
Pressurization JP5
Enabled
Jumpered
Disabled
Open
JP6 - Authorization
This jumper allows activation or non-activation of the pump/dispenser from an external source
[for example, an Fuel Management System (FMS)]. When jumpered, a 115/230 VAC signal
must be present on the Control Feed/authorization line (refer to the wiring diagram for your
model pump/dispenser) for pump activation to occur (required setting for Gasboy Series
1000). When open, the Control Feed line signal is ignored (required setting for Standalone
mode).
Authorization
JP6
Enabled
Jumpered
Disabled
Open
Note: For JP6 Authorization, in Standalone mode, the authorization signal must be present to
activate the pump.