Jp2 - mode, Jp3, jp4 - leak detect delay, Jp5 - hose pressurization – Gasboy 9800 Atlas User Manual

Page 12: Jp6 - authorization

background image

Installing Atlas 9800 CPU Board (M06333KXXXX)

Page 12

MDE-4652D Atlas™ 9800 Electronics Field Installation Instructions · April 2013

JP2 - Mode

This jumper selects the mode in which the pump/dispenser operates. Set the mode to “Online”
if the pump/dispenser communicates to a controlling system (for example, Gasboy TopKAT

or CFN System). Set the mode to “Standalone” for all other configurations (for example,
Gasboy Series 1000 Fuel Management System or no controlling system).

Mode

JP2

Standalone Jumpered

Online

Open

JP3, JP4 - Leak Detect Delay

These jumpers select the delay time used by leak detectors in Submersible Turbine Pump
(STP) applications. The delay time is the period between the activation of the submersible
pump and the activation of the slow flow valve. The delay time must be set according to the
type of leak detector installed on the STP to allow for a normal leak test for each transaction.
The delay time must be set to 0 seconds for suction pumps.

Delay Time JP3

JP4

0 seconds

Jumpered

Jumpered

4 seconds

Jumpered

Open

5 seconds

Open

Jumpered

6 seconds

Open

Open

JP5 - Hose Pressurization

For US Gallons (always in Hose Pressurization mode), this jumper is ignored. This jumper is
used to determine if hose pressurization is used. If enabled, the slow flow valve is opened
before reset is complete, to allow the hose to be pressurized before fuel dispensing begins.

Pressurization JP5

Enabled

Jumpered

Disabled

Open

JP6 - Authorization

This jumper allows activation or non-activation of the pump/dispenser from an external source
[for example, an Fuel Management System (FMS)]. When jumpered, a 115/230 VAC signal
must be present on the Control Feed/authorization line (refer to the wiring diagram for your
model pump/dispenser) for pump activation to occur (required setting for Gasboy Series
1000). When open, the Control Feed line signal is ignored (required setting for Standalone
mode).

Authorization

JP6

Enabled

Jumpered

Disabled

Open

Note: For JP6 Authorization, in Standalone mode, the authorization signal must be present to

activate the pump.