Optional intop tissues – Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 95

9424200892 Rev F
87
Part
Tissue Description
Nr
Implemented
Y/n/a
7-2
30
control parameter T
Y
31
Typo
n/a
32
Typo in syntax
n/a
35
Typo Syntax Control time
n/a
36
Syntax parameter DSet-Ref missing
Y
37
Syntax GOOSE "T" type
Y
39
Add DstAddr to GoCB
Y
40
GOOSE Message “AppID” to “GoID”
Y
41
GsCB “AppID” to “GsID”
Y/
42
SV timestamp: “EntryTime” to “TimeStamp"
n/a
43
Control "T" semantic
Y
44
AddCause - Object not sel
n/a
45
Missing AddCauses (neg range)
n/a
46
Synchro check cancel
n/a
47
"." in LD Name?
Y
49
BRCB TimeOfEntry (part of #453)
-
50
LNName start with number?
Y
51
ARRAY [0..num] missing
Y
52
Ambiguity GOOSE SqNum
N
53
Add DstAddr to GsCB, SV
N
151
Name constraint for control blocks etc.
Y
166
DataRef attribute in Log
n/a
185
Logging - Integrity periode
n/a
189
SV Format
n/a
190
BRCB: EntryId and TimeOfEntry (part of #453)
-
191
BRCB: Integrity and buffering reports (part of #453)
-
234
New type CtxInt (Enums are mapped to 8 bit integer)
n/a
275
Confusing statement on GI usage (part of #453)
-
278
EntryId not valid for a server (part of #453)
-
Part 6
1
Syntax
n/a
5
tExtensionAttributeNameEnum is restricted
Y
8
SIUnit enumeration for W
Y
10
Base type for bitstring usage
Y
17
DAI/SDI elements syntax
Y
169
Ordering of enum differs from 7-3
n/a
Notes:
Tissue 49, 190, 191, 275 and 278 are part of the optional tissue #453, all other technical tissues in the
table are mandatory if applicable.
Editorial tissues are marked as “n/a”.
Final proposal on tissue 45 is not defined yet.
Optional IntOp Tissues
After the approval of the server conformance test procedures version 2.2 the following IntOp tissues in
Table X were added or changed. It is optional to implement these tissues.
Table 32. Optional IntOp Tissues
Part
Tissue
Nr
Description
Implemented
Y/N/n/a
8-1
246
Control negative response (SBOns) with LastApplError
n/a
8-1
545
Skip file directories with no files
Y
BE1-11
Conformance Statements